Aluminum Wiring in Older Homes
Aluminum wiring, the single-strand kind used for branch circuits in homes built between 1965 and the mid-1970s, is a real fire risk, but the danger is at the connections, not in the wire itself. The CPSC accepts three permanent fixes: rewiring with copper, COPALUM crimp connectors, or AlumiConn connectors.
If your house is from that era, the first job is finding out whether it has single-strand aluminum branch circuits at all. Not every home from those years has it. If yours does, the fix does not have to mean tearing out every wire.
The CPSC says homes built before 1965 are unlikely to have aluminum branch circuits. An addition, garage conversion or rewiring done between 1965 and the mid-1970s could. Aluminum was also used for dryer and range circuits, which is a different, heavier wire.
See how to checkThis is the period the CPSC warns about. Look for “AL” or “ALUMINUM” printed on cable in the attic, garage or near the panel. If you find it, or you can’t tell, have the wiring inspected before you add circuits or sell.
Request a wiring checkThe single-strand aluminum branch wiring the CPSC warns about was installed between 1965 and the mid-1970s. A house built later is unlikely to have it, but check any older section of the home.
See how to checkThe year built is on your county appraisal record and usually in your closing papers. San Angelo’s median home was built in 1977, so many houses here fall close to the period in question.
See how to checkIs Aluminum Wiring Safe?
Not in its original form. A CPSC survey found that homes built before 1972 and wired with aluminum were 55 times more likely than copper-wired homes to have at least one outlet connection reach “fire hazard conditions.” The survey covered outlet connections only, and the CPSC has no comparable data for aluminum-wired homes built after 1972.
The wire itself carries current fine. The trouble is where it meets a screw terminal or a splice. Insurer State Auto describes the result as loose connections that can lead to overheating, arcing and sparking, inside walls where a fire can grow before anyone notices.
How to Identify Aluminum Wiring
- Check the wire color. Aluminum is dull silver. Copper is orange-brown. Only look at bare ends where they are already visible; do not open outlets or the panel to look.
- Know the look-alike. Cable marked “CU-clad” or “copper-clad” is aluminum with a copper coating. The CPSC’s repair advice does not cover it.
- Separate the big circuits. Thick stranded aluminum feeding the service, an electric dryer or a range is a different product. The CPSC repairs below are for 15 and 20 amp branch circuits only.
- Read the cable jacket. The CPSC says cable with aluminum conductors has “Al” or “Aluminum” printed along its length. Look where cable is exposed: the attic, an unfinished garage, or where it enters the panel.
Warning Signs at Outlets and Switches
The CPSC notes that failing aluminum connections seldom give easy warnings. When they do, the signs are:
- Flickering lights
- Outlets or circuits that stop working
- A smell of burning plastic at an outlet or switch
- Cover plates on outlets or switches that are warm or hot to the touch

Aluminum Wiring Repair Options Compared
| Method | How it works | CPSC position |
|---|---|---|
| Rewire with copper | New copper circuits replace the aluminum | Permanent. The best method, but often impractical or expensive |
| COPALUM crimp | A short copper pigtail is crimped to each aluminum wire with a special tool | Permanent. Installed only by electricians trained by the manufacturer |
| AlumiConn connector | A set-screw lug joins aluminum and copper in separate ports | Permanent, acceptable alternative where COPALUM is not available |
| CO/ALR outlets and switches | Devices rated for aluminum wire | “At best, an incomplete repair” |
| Twist-on wire connectors | Copper pigtails joined with wire nuts | Not a recommended repair; emergency use only |
Source: CPSC, Repairing Aluminum Wiring (Publication 516).
COPALUM
The CPSC calls COPALUM a permanent repair. The catch is that only manufacturer-trained electricians with the crimp tool can install it, so it is not always available locally.
AlumiConn
AlumiConn connectors are UL 486C listed and made for #12 and #10 solid aluminum joined to copper, with each wire in its own port and a set torque for each screw. The CPSC accepts them where COPALUM is not available, while noting they have a shorter track record.
Rewiring
A full copper rewire removes the problem for good and lets you add grounding, GFCI and AFCI protection at the same time. It is also the most expensive route: a whole-house rewire typically runs $6,000 to $17,000 in Texas. Our electrical wiring page covers rewiring and repairs.
Aluminum Wiring in San Angelo Homes
Census figures show 5,609 homes in San Angelo built in the 1960s and 6,555 built in the 1970s, out of 45,574. The median home here was built in 1977. That is about one home in four built in the 1960s and 1970s, the two decades that contain the CPSC’s 1965 to mid-1970s window. There is no count of how many have aluminum branch wiring, so the only way to know is to check, ideally before you buy, sell or add circuits. Homes from this era may also have their original panels; if yours says Federal Pacific, read our guide on Federal Pacific panels too.
Aluminum Wiring and Homeowners Insurance
Insurer Hippo says insurers can charge a higher rate or deny coverage for homes with aluminum wiring, and may require repairs after an inspection. If you are buying a house from this era, ask your agent before closing. If you already own one, keep the report from an electrical inspection and the receipts for any COPALUM or AlumiConn repairs; they are your proof the hazard was dealt with.
Questions About Aluminum Wiring
Do I have to rewire a house with aluminum wiring?
No. The CPSC accepts three permanent repairs: a copper rewire, COPALUM crimp connectors, or AlumiConn connectors where COPALUM is not available. Rewiring is the most complete fix and the most expensive.
Can I repair aluminum wiring myself?
The CPSC strongly recommends hiring a qualified electrician, and COPALUM connectors can only be installed by electricians trained by the manufacturer. A bad aluminum connection is the hazard, so a poorly made repair can be worse than none.
Are purple wire nuts safe for aluminum wire?
The CPSC does not recommend twist-on wire connectors as a repair for aluminum branch wiring. It says they do not solve the overheating problem and should be used only as an emergency, temporary fix.
Are CO/ALR outlets enough?
Not by themselves. CPSC staff call CO/ALR devices at best an incomplete repair, because they have failed in laboratory tests and are not available for every part of the system.
Is the aluminum wire to my dryer or range a problem?
That heavier stranded wire is a different product, and the CPSC’s branch circuit repairs do not apply to it. Its connections still need to be tight and made with parts rated for aluminum, so have them checked if you see heat damage.